Related Contents With 61F-G1 Floatless Level Controller, the water level of a water supply is above the E2' height, but the pump does not operate. What is the cause of the problem and how can it be corrected? The U1 Relay Unit is not self-holding because of a disconnection or poor contact between the E2' electrode and its cable. Momentarily short the E1' and E3 terminals of the 61F-G1 Controller to operate self-hold the U1 Relay Unit. When the U1 Relay Unit will not operate self-holdreplace the U1 Relay Unit. Also, check whether there is a damaged cable between the 61F Controller and electrode, and check whether the E2' electrode is coated with tarnish or oil. As an emergency measure, operation can be forced by shorting the E1' and E3 terminals on the 61F-G1 Controller, however, idling cannot be prevented in this case. Level Controller: Pump Does Not Operate Though Water Level is Above E2 Height. With 61F-G1 Floatless Level Controller, the water level of a water supply is above the E2' height, but the pump does cara memasang omron 61f g1 ap oil operate. The following items may be the cause, cara memasang omron 61f g1 ap oil check these. A power interruption occurred and the U1 Relay Unit was reset. Other Level Switches FAQ. Is it possible to use a commercially available terminal block or to make one yourself, instead of using the one that comes with the K7L? How long is your longest Liquid Leakage Sensing Band?